Simple mode parameter list
Basic settings
5 - 6
쑶
I001746E
Fig. 5-4:
Setting the starting torque
NOTES
A too large setting will cause the motor to overheat, resulting in an over current trip (OL (over cur-
rent alarm) then E.OC1 (over current shutoff during acceleration)), thermal trip (E.THM (Motor
overload shutoff ), and E.THT (Inverter overload shutoff )).
When an error (E.OC1) occurs, release the start command, and decrease the value 1% by 1%. (Refer
If the inverter still does not operate properly after the above measures, adjust the acceleration/
deceleration setting or activate the vector control function by Pr. 80 "Motor capacity". (Refer to
section 6.3.2.)
햲
Screen at powering on
The monitor display appears.
햳
Press the PU/EXT key to choose the PU
operation mode.
햴
Press the MODE key to choose the parameter
setting mode.
햵
Turn the digital dial until P.0 (Pr. 0) appears.
햶
Press the SET key to show the currently set value.
"6.0" (initial value is 6% for motors up to 0.75 kW)
appears.
햷
Turn the digital dial to change it
to the setting value of "7.0" (7.0%).
햸
Press the SET key to set.
Operation
Display
The parameter number read previously appears.
Flicker ... Parameter setting complete!
PU indication is lit.
The initial value differs
according to the
capacity.
앫
By turning the digital dial, you can read another parameter.
앫
Press the SET key to show the setting again.
앫
Press the SET key twice to show the next parameter.
PRM indication is lit.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......