Basic settings
Simple mode parameter list
FR-E700 SC EC/ENE
5 - 5
5.1.3
Increase the starting torque (Pr. 0)
Set this parameter when the motor with a load does not rotate, an alarm OL is output, resulting in an
inverter trip due to OC1, etc.
Pr.
No.
Name
Initial Value
Setting
Range
Description
0
Torque boost
FR-E720S-008SC to 050SC
FR-E740-016SC and 026SC
6%
0–30%
Motor torque in the low-frequency range can be adjusted to the
load to increase the starting motor torque.
FR-E720S-080SC and 110SC
FR-E740-040SC to 095SC
4%
FR-E740-120SC and 170SC
3%
FR-E740-230SC and 300SC
2%
Example
쑴
When the motor with a load does not rotate, increase the Pr. 0 value 1% by 1% unit by looking at
the motor movement. (The guideline is for about 10% change at the greatest.)
Fig. 5-3:
Relation between output frequency and output
voltage
I001098E
V/F
V/F
V/F
Setting
range
Pr. 0, Pr. 46
Output v
oltage
Base
frequency
Output frequency [Hz]