Parameter overview
Parameter
6 - 20
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter-
Copy
Para-
meter
Clear
All
Para-
meter
Clear
Refer
to
Page
Rela
te
d
Paramet
ers
✔
: Enabled
—: Disabled
Par
amet
er unit
language swit
cho
ver
145
PU display language selection
1
1
0
Japanese
✔
—
—
1
English
2
German
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
—
146
Parameter for manufacturer setting. Do not set.
—
147
Refer to Pr. 7 and Pr. 8
Det
ec
tion of output curr
en
t (
Y12 signal)
and D
et
ec
tion of z
er
o curr
en
t (
Y13 signal)
150
Output current detection level
0.1%
150%
0–200%
Set the output current detection level. 100%
is the rated inverter current.
✔
✔
✔
151
Output current detection
signal delay time
0.1 s
0 s
0–10 s
Set the output current detection period. Set
the time from when the output current has
risen above the setting until the output
current detection signal (Y12) is output.
✔
✔
✔
152
Zero current detection level
0.1%
5%
0–200%
Set the zero current detection level. Suppose
that the rated inverter current at the
specified overload capacity is 100%.
✔
✔
✔
153
Zero current detection time
0.01 s
0.5 s
0–1 s
Set this parameter to define the period from
when the output current drops below the Pr.
152 value until the zero current detection
signal (Y13) is output.
✔
✔
✔
—
156
157
Refer to Pr. 22
—
158
Refer to Pr. 52
User gr
oup func
tion
160
User group read selection
1
0
0
Simple mode and extended mode
parameters can be displayed.
✔
✔
✔
1
Only parameters registered in the user group
can be displayed.
9999
Only the simple mode parameters can be
displayed
172
User group registered display/
batch clear
1
0
(0–16)
Displays the number of cases registered as a
user group (reading only).
✔
—
—
9999
Batch clear the user group registration
173
User group registration
1
9999
0–999/9999
Set the parameter numbers to be registered
to the user group.
Read value is always "9999".
—
—
—
174
User group clear
1
9999
0–999/9999
Set the parameter numbers to be cleared
from the user group.
Read value is always "9999".
—
—
—
Tab. 6-1:
Parameter overview (20)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......