Frequency setting by analog input (terminal 2, 4)
Parameter
6 - 182
6.16.2
Input filter time constant (Pr. 74)
If the set point signal (terminal 2 or 4) is an unstable signal or contains noise you can filter out the in-
stability or noise by increasing the setting value of Pr. 74.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Increase the filter time constant if steady operation cannot be performed due to noise. A larger setting
results in slower response. (The time constant can be set between approximately 5 ms to 1 s with the
setting of 0 to 8.)
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
74
Input filter time constant
1
0–8
Set the primary delay filter time constant for the
analog input.
A larger setting results in a larger filter.
—