Function assignment of external terminals
Parameter
6 - 128
햲
Note that when the frequency setting is varied using an analog signal or the digital dial of the
operation panel, the output of the SU (up to frequency) signal may alternate on and off depend-
ing on that varying speed and the timing of the varying speed due to acceleration/deceleration
time setting. (The output will not alternate on and off when the acceleration/deceleration time
setting is "0 s".)
80
180
SAFE
Safety monitor output
Output while safety stop func-
tion is activated.
—
81
181
SAFE2
Safety monitor output 2
The signal is output when no
internal safety circuit failure
(E.SAF, E.6, E.7, E.CPU) exists.
—
90
190
Y90
Life alarm
Output when any of the control
circuit capacitor, main circuit
capacitor and inrush current
limit circuit or the cooling fan
approaches the end of its ser-
vice life.
Pr. 255–Pr. 259
91
191
Y91
Alarm output 3 (power-off signal)
Output when an error occurs
due to the circuit failure or con-
nection alarm of the inverter.
—
93
193
Y93
Current average value monitor
signal
Average current value and
maintenance timer value are
output as pulses. The signal can
not be set in Pr. 192 "ABC termi-
nal function selection".
Pr. 555–Pr. 557
95
195
Y95
Maintenance timer signal
Output when Pr. 503 rises to or
above the Pr. 504 setting.
Pr. 503, Pr. 504
96
196
REM
Remote Output
Output to the terminal when a
value is set to the parameter.
Pr. 495–Pr. 497
98
198
LF
Minor fault output
Output when a minor fault (fan
failure or communication error
warning) occurs.
Pr. 121, Pr. 244
99
199
ALM
Alarm output
Output when the inverter's pro-
tective function is activated to
stop the output (major fault).
The signal output is stopped
when a reset turns on.
—
9999
—
No function
—
—
—
NOTES
The same function may be set to more than one terminal.
When the function is executed, the terminal conducts at the setting of any of "0" to "99", and does
not conduct at the setting of any of "100" to "199".
Changing the terminal assignment using Pr. 190 to Pr. 192 "Output terminal function selection"
may affect the other functions. Make setting after confirming the function of each terminal.
Do not assign signals which repeat frequent ON/OFF to A, B, and C. Otherwise, the life of the relay
contact decreases.
Setting
Terminal
Function
Operation
Related Parameters
Refer to
Page
Source
Logic
Sink
Logic
Tab. 6-31:
Output terminal function assignment (2)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......