Parameter
Misoperation prevention and parameter setting restriction
FR-E700 SC EC/ENE
6 - 199
User group function (Pr. 160, Pr. 172 to Pr. 174)
The user group function is designed to display only the parameters necessary for setting.
From among all parameters, a maximum of 16 parameters can be registered to a user group. When Pr.
160 is set to "1", only the parameters registered to the user group can be accessed. (Reading of pa-
rameters other than the user group registration is disabled.)
To register a parameter to the user group, set its parameter number to Pr. 173. To delete a parameter
from the user group, set its parameter number to Pr. 174. To batch-delete the registered parameters,
set Pr. 172 to "9999".
Registration of parameter to user group (Pr. 173)
I001821E
Fig. 6-100:
When registering Pr. 3 to user group
햲
Confirmation of the RUN indication and
operation mode indication.
The inverter must be at a stop.
The inverter must be in the PU operation mode
(using the PU/EXT key).
햳
Press the MODE key to choose the parameter
setting mode.
햴
Turn the digital dial until P.173 (Pr. 173) appears.
햵
Press the SET key to display "9999".
햶
Turn the digital dial until "3" appears.
햷
Press the SET key to set.
"P.173" and "3" are displayed alternately.
To continue parameter registration, repeat
steps
햴
to
햷
.
Operation
Display
Flicker ... Registration of Pr. 3
to user group completed!
Parameter setting mode
Pr. 173 "User group
registration" is displayed.
When Pr. 173 is read, "9999" is
displayed.
Select the parameter number
to be registered.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......