Control circuit specifications
Wiring
3 - 18
3.4.1
Control circuit terminals
Wiring method
Use a bar terminal and a cable with a sheath stripped off for the control circuit wiring. For a single wire,
strip off the sheath of the cable and apply directly.
햲
Remove about 10 mm of the cable insulation. Wire the stripped cable after twisting it to prevent
it from becoming loose. In addition, do not solder it.
햳
Insert wires to a bar terminal, and check that the wires come out for about 0 to 0.5 mm from a
sleeve.
I002125E
Fig. 3-7:
Terminal layout
I002126E
Fig. 3-8:
Preparation of the cable
Fig. 3-9:
Fixing of bar terminals
I001984E
STF
RES
STR
SD
PC
RH
RM
RL
AM
C
B
A
10
2
5
4
RUN
SE
FU
S1
S2
PC
Recommended wire size:
0.3 mm
2
to 0.75 mm
2
10 mm
Sleeve
Cable
Shell
0–0.5
mm