Parameter
Function assignment of external terminals
FR-E700 SC EC/ENE
6 - 133
6.10.7
Output current detection function (Y12, Y13, Pr. 150 to Pr. 153)
The output power during inverter running can be detected and output to the output terminal.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Output current detection (Y12, Pr. 150, Pr. 151, Pr. 166, Pr. 167)
The output current detection function can be used for excessive torque detection, etc.
If the output current remains higher than the Pr. 150 setting during inverter operation for longer than
the time set in Pr. 151, the output current detection signal (Y12) is output from the inverter's open col-
lector or relay output terminal. When the Y12 signal turns on, the ON state is held for approximately
100 ms.
For the Y12 signal, set "12 (positive logic) or 112 (negative logic)" in Pr. 190 to Pr. 192 "Output terminal
function selection" and assign functions to the output terminal.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
150
Output current detection level
150%
0–200%
Set the output current detection level. 100% is the
rated inverter current.
190–192 Output terminal
function selection
151
Output current detection signal
delay time
0 s
0–10 s
Set the output current detection period. Set the time
from when the output current has risen above the
setting until the output current detection signal
(Y12) is output.
152
Zero current detection level
5%
0–200%
Set the zero current detection level.
The rated inverter current is assumed to be 100%.
153
Zero current detection time
0.5 s
0–1 s
Set this parameter to define the period from when
the output current drops below the Pr. 152 value
until the zero current detection signal (Y13) is
output.
I001155E
Fig. 6-63:
Output current detection
Output current
Pr. 150
Output current
detection signal Y12
Pr. 151
100 ms
Time
ON
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......