Basic settings
PU operation mode
FR-E700 SC EC/ENE
5 - 29
I001774E
Fig. 5-20:
Operate the inverter by using the analog current input
NOTES
One of Pr. 178 to Pr. 184 "Input terminal function selection" must be set to "4" (AU signal) (initial
value). (Refer to section 6.10.1.)
Change the frequency (50 Hz) at the maximum value of potentiometer (at 20 mA) by adjusting the
frequency in Pr. 126 "Terminal 4 frequency setting gain frequency". (Refer to section 5.3.6).
Change the frequency (0 Hz) at the minimum value of potentiometer (at 4 mA) by adjusting the
frequency in calibration parameter C5 "Terminal 4 frequency setting bias frequency". (Refer to sec-
tion 6.16.3.)
햲
Screen at powering on
The monitor display appears.
햳
Change the Pr. 79 setting to "4".
(Refer to section 4.3.3 for change of the setting.)
"PU" display and "EXT" display are lit.
햴
Check that the terminal 4 input selection signal (AU)
is on.
Turn on the start switch RUN.
When the frequency command is not given,
"RUN" flickers fast.
햵
Acceleration
constant speed
Perform 20 mA input. The frequency value on the
indication increases according to Pr. 7
"Acceleration time" until 50 Hz is displayed.
햶
Deceleration
Perform 4mA input. The frequency value on the
indication decreases according to Pr. 8
"Deceleration time" and displays "0.00" (0.00 Hz)
when the motor is stopped.
"RUN" flickers fast.
햷
Press the STOP/RESET key
"RUN" turns off.
Operation
Display
Flickering
Flickering
Stop
Current signal
source
(0/4–20 mA DC)
Current signal
source
(0/4–20 mA DC)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......