Parameter
Frequency setting by analog input (terminal 2, 4)
FR-E700 SC EC/ENE
6 - 183
6.16.3
Bias and gain of frequency setting voltage (current)
[Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) to C7 (Pr. 905)]
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency set-
ting signal (0 to 5 V, 0 to 10 V or 0/4 to 20 mA DC).
These parameters can be used to configure the inverter precisely for set point signals that either ex-
ceed or do not quite reach 5 V or 10 V or 20 mA. These settings can also be used to configure inverse
control (i.e. high output frequency at minimum set point signal, minimum output frequency at max-
imum set point signal).
햲
The above parameters can be set when Pr. 160 "User group read selection" = 0.
햳
The parameter number in parentheses is the one for use with the operation panel (PA02) for the
FR-E500 series or parameter unit (FR-PU04/FR-PU07).
햴
The above parameter allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Pr. No.
Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
125
Terminal 2 frequency setting gain
frequency
50 Hz
0–400 Hz
Set the frequency of terminal 2 input gain
(maximum).
20
73
267
79
Acceleration/
deceleration reference
frequency
Analog input selection
Terminal 4 input
selection
Operation mode
selection
126
Terminal 4 frequency setting gain
frequency
50 Hz
0–400 Hz
Set the frequency of terminal 4 input gain
(maximum).
241
Analog input display unit
switchover
햲 햴
0
0
Displayed in %
Select the unit of
analog input display.
1
Displayed in V/mA
C2
(902)
Terminal 2 frequency setting bias
frequency
햲 햳
0 Hz
0–400 Hz
Set the frequency on the bias side of
terminal 2 input.
C3
(902)
Terminal 2 frequency setting
bias
햲 햳
0%
0–300%
Set the converted % of the bias side voltage
(current) of terminal 2 input.
C4
(903)
Terminal 2 frequency setting
gain
햲 햳
100%
0–300%
Set the converted % of the gain side voltage
of terminal 2 input.)
C5
(904)
Terminal 4 frequency setting
bias frequency
햲 햳
0 Hz
0–400 Hz
Set the frequency on the bias side of
terminal 4 input.
C6
(904)
Terminal 4 frequency setting
bias
햲 햳
20%
0–300%
Set the converted % of the bias side current
(voltage) of terminal 4 input.
C7
(905)
Terminal 4 frequency setting
gain
햲 햳
100%
0–300%
Set the converted % of the gain side current
(voltage) of terminal 4 input.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......