Parameter
Frequency setting by analog input (terminal 2, 4)
FR-E700 SC EC/ENE
6 - 177
6.16
Frequency setting by analog input (terminal 2, 4)
6.16.1
Analog input selection (Pr. 73, Pr. 267)
You can select the function that switches between forward rotation and reverse rotation according to
the analog input terminal specifications and input signal.
The following settings are possible:
●
Select reference voltages and currents: 0–10 V, 0–5 V or 0/4–20 mA
●
Suppress motor reversing
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Purpose
Parameters that must be set
Refer to
Section
Selection of voltage/current input
(terminal 2, 4)
Perform forward/reverse rotation by
analog input.
Analog input selection
Pr. 73, Pr. 267
Adjustment (calibration) of analog
input frequency and voltage (current)
Bias and gain of frequency setting voltage
(current)
Pr. 125, Pr. 126,
Pr. 241, C2–C7
(Pr. 902–Pr. 905)
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
73
Analog input
selection
1
0
Terminal 2: 0–10 V
Without reversible operation
125
126
C2
–
C7
Terminal 2 frequency
setting gain frequency
Terminal 4 frequency
setting gain frequency
Terminal 2 frequency
setting bias frequency
to
Terminal 4 frequency
setting gain
1
Terminal 2: 0–5 V
10
Terminal 2: 0–10 V
With reversible operation
11
Terminal 2: 0–5 V
267
Terminal 4 input
selection
0
Voltage/Current Input Switch
Description
0
Terminal 4: 0/4–20 mA
1
Terminal 4: 0–5 V
2
Terminal 4: 0–10 V
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......