Parameter
Acceleration and deceleration
FR-E700 SC EC/ENE
6 - 71
6.7
Acceleration and deceleration
6.7.1
Acceleration and deceleration time
(Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 147)
Used to set motor acceleration/deceleration time. Set a larger value for a slower speed increase/de-
crease or a smaller value for a faster speed increase/decrease.
햲
The above parameters can be set when Pr. 160 "User group read selection" = 0.
햳
Depends on the Pr. 21 "Acceleration/deceleration time increments" setting. The initial value for
the setting range is "0 to 3600 s" and the setting increments is "0.1 s".
Purpose
Parameters that must be set
Refer to
Section
Motor acceleration/deceleration time
setting
Acceleration/deceleration times
Pr. 7, Pr. 8, Pr. 20,
Pr. 21, Pr. 44,
Pr. 45, Pr. 147
Starting frequency
Starting frequency and start-time hold
Pr. 13, Pr. 571
Set acceleration/deceleration
pattern suitable for application
Acceleration/deceleration pattern
Pr. 29
Automatically set optimum
acceleration/deceleration time
Automatic acceleration/deceleration
Pr. 61–Pr. 63,
Pr. 292
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
7
Acceleration time
FR-E720S-110SC or less,
FR-E740-095SC or less
5 s
0–3600 s/
0–360 s
햳
Set the motor acceleration time.
3
29
125
126
178–184
Base frequency
Acceleration/deceleration
pattern selection
Frequency setting gain
frequency
Frequency setting gain
frequency
Input terminal function
selection
FR-E740-120SC and 170SC
10 s
FR-E740-230SC and 300SC
15 s
8
Deceleration time
FR-E720S-110SC or less,
FR-E740-095SC or less
5 s
0–3600 s/
0–360 s
햳
Set the motor deceleration time.
FR-E740-120SC and 170SC
10 s
FR-E740-230SC and 300SC
15 s
20
Acceleration/
deceleration
reference
frequency
햲
50 Hz
1–400 Hz
Set the frequency that will be the basis
of acceleration/deceleration time.
As acceleration/deceleration time, set
the frequency change time from stop to
Pr. 20.
21
Acceleration/
deceleration time
increments
햲
0
0
Increments:
0.1 s
Range:
0–3600 s
Increments and
setting range of
acceleration/
deceleration time
setting can be
changed.
1
Increments:
0.01 s
Range:
0–360 s
44
Second
acceleration/
deceleration time
햲
FR-E720S-110SC or less,
FR-E740-095SC or less
5 s
0–3600 s/
0–360 s
햳
Set the acceleration/deceleration time
when the RT signal is on.
FR-E740-120SC and 170SC
10 s
FR-E740-230SC and 300SC
15 s
45
Second
deceleration time
햲
9999
0–3600 s/
0–360 s
햳
Set the deceleration time when the RT
signal is on.
9999
Acceleration time = deceleration time
147
Acceleration/
deceleration time
switching
frequency
햲
9999
0–400 Hz
Frequency when automatically
switching to the acceleration/
deceleration time of Pr. 44 and Pr. 45.
9999
No function
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......