Wiring
Terminal connection diagram
FR-E700 SC EC/ENE
3 - 5
3.2.2
FR-E700 SC ENE
I002123E_ENE
Fig. 3-4:
Terminal connection diagram of the inverter FR-E700 SC ENE
R/L1
P1
P/+
PR
N/-
S/L2
T/L3
U
V
W
FU
RUN
SE
A
B
C
AM
5
2
10(+5V)
2
3
1
5
*1
*7
*3
V
I
*5
R
(+)
(-)
L1
N
*6
(+)
(-)
4
*5
STR
STF
RH
RM
RL
RES
SD
PC *2
S1
S2
SINK
SOURCE
24V
*6
*6
*8
Source Logic
Main circuit terminal
Control circuit terminal
Jumper
*1 DC reactor
When connecting a DC reactor, remove the jumper
across P1 and P/+.
Earth
Motor
3-phase AC
power supply
Main circuit
Control circuit
Terminal functions vary with
the input terminal assign-
ment set in Pr. 178 to 182 and
184.
Control input signals (No voltage input allowed)
Forward
rotation start
Reverse
rotation start
High speed
Middle speed
Low speed
Multi-speed selection
Reset
Contact input common (sink*)
24 V DC power supply/
max. 100 mA load current
Contact input common (source*)
*(Common for external power supply transistor)
Frequency setting signal (analog)
0–5 V DC
4–20 mA DC
0–5 V DC
0–10 V DC
PU
connector
*4 It is recommended to use
2 W/1 k when the
frequency setting signal is
changed frequently.
Relay output
(Alarm output)
Relay output
Running
Terminal functions vary with
the input terminal assignment
set in Pr. 192.
Frequency detection
Open collector output common
Sink/source common
Analog signal output
(0–10 V DC)
*4
Frequency
setting
potentiometer
1/2W, 1k
M
3~
Earth
Brake unit
(Option)
*7 Brake resistor (FR-ABR)
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
(The brake resistor can not be connected to the
FR-E720S-008SC and 015SC.)
Earth
Terminal functions vary with the output
terminal assignment set in Pr. 190 and
191.
Open collector output
USB
connector
*2 When using terminals
PC-SD as a 24 V DC
power supply, take
care not to short
across terminals PC-SD.
(0–10 V DC)
Voltage/current input
switch
Terminal 4 input
(Current input)
*5 Terminal input specifications can be changed by analog input
specifications switchover (Pr. 267) Set the voltage/current input
switch in the "V" position to select voltage input (0 to 5 V/0 to10
V) and "I" (initial value) to select current input (4 to 20 mA). To
use terminal 4 (initial setting is current input), set "4" in any of
Pr. 178 to Pr. 184 (input terminal function selection)to assign the
function, and turn ON AU signal.
*3 Terminal input specifica-
tions can be changed by
analog input specifica-
tions switchover (Pr. 73).
(Analog common)
*6 A brake transistor is not built-in to the
FR-E720S-008SC and 015SC.
1-phase AC
power supply
Inrush current
limit circuit
Output shutoff
circuit
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Shorting
wire
MCCB
MC
MCCB
MC
Single-phase power input
*8 A personal computer can be connected via the
USB mini B connector (USB 1.1).
You can perform parameter setting and
monitoring with the commissioning software
tool FR Configurator2.
Ethernet
connector
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......