Parameter
MODBUS®/TCP (FR-E700 SC ENE)
FR-E700 SC EC/ENE
6 - 335
Function code list
Function name
Read/
write
Code
Outline
Message
format
Refer to
page
Read holding
register
Read
H03
The data of the holding registers is read.
The various data of the inverter can be read from MODBUS®
registers.
System environmental variable (Refer to page 6-345.)
Real time monitor (Refer to page 6-140.)
Faults history (Refer to page 6-348.)
Inverter parameters (Refer to page 6-347.)
Preset single
register
Write
H06
Data is written to a holding register.
Data can be written to MODBUS® registers to output instructions
to the inverter or set parameters.
System environmental variable (Refer to page 6-345.)
Inverter parameters (Refer to page 6-347.)
Diagnostics
Read
H08
Functions are diagnosed. (communication check only)
A communication check can be made since the query message is
sent and the query message is returned as it is as the return mes-
sage (subfunction code H00 function).
Subfunction code H00 (Return query data)
Preset multiple
registers
Write
H10
Data is written to multiple consecutive holding registers.
Data can be written to consecutive multiple MODBUS® registers to
output instructions to the inverter or set parameters.
System environmental variable (Refer to page 6-345.)
Inverter parameters (Refer to page 6-347.)
Read holding
register access log
Read
H46
The number of registers that were successfully accessed by the
previous communication is read.
Queries by function codes H03 and H10 are supported.
The number and start address of holding registers successfully
accessed by the previous communication are returned.
"0" is returned for both the number and start address for queries
other than function code H03 and H10.
When the connection is closed, the data in the log is cleared.
Tab. 6-123:
Function codes
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......