Parameter
Monitor display and monitor output signals
FR-E700 SC EC/ENE
6 - 145
Operation panel (FR-DU07) I/O terminal monitor
When Pr. 52 is set to any of "55 to 57", the I/O terminal states can be monitored on the operation panel.
The I/O terminal monitor is displayed on the third monitor.
The LED is on when the terminal is on, and the LED is off when the terminal is off. The centre line of LED
is always on.
햲
You can set "56" or "57" even if the option is not fitted. When the option is not fitted, the monitor
displays are all off.
On the unit I/O terminal monitor (Pr. 52 = "55"), the upper LEDs denote the input terminal states and
the lower the output terminal states.
On the option FR-A7AX-Ekit-SC-E monitor (Pr. 52 = 56), the decimal point LED of the first digit LED is on.
On the option FR-A7AY-Ekit-SC-E or FR-A7AR-Ekit-SC-E monitor (Pr. 52 = "57"), the decimal point LED
of the second digit LED is on.
Pr. 52
Monitor Description
55
Displays the I/O and output terminal ON/OFF states of the inverter unit.
56
햲
Displays the input terminal ON/OFF states of the digital input option (FR-A7AX-Ekit-SC-E).
57
햲
Displays the output terminal ON/OFF states of the digital output option (FR-A7AY-Ekit-SC-E)
or relay output option (FR-A7AR-Ekit-SC-E).
Tab. 6-37:
I/O terminal monitor
I001802E
Fig. 6-70:
Displaying the signal states of the I/O terminals
I001803E
Fig. 6-71:
Displaying the signal states when the option FR-A7AX-Ekit-SC-E is mounted
I001163E
Fig. 6-72:
Displaying the signal states when the option FR-A7AY-Ekit-SC-E or FR-A7AR-Ekit-SC-E is mounted
Output
terminals
Centre line is
always on
Display example:
When signals STF, RH and
RUN are on
Input
terminal
Decimal point LED of first digit LED is always on
Centre line is always on
Decimal point LED of second digit LED is always on
FR-A7AY-Ekit-SC-E
Centre line is always on
FR-A7AR-Ekit-SC-E
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......