Troubleshooting
Check first when you have troubles
FR-E700 SC EC/ENE
7 - 23
7.6
Check first when you have troubles
7.6.1
Motor does not start
Check Points
Possible Cause
Countermeasures
Refer to
Page
Main circuit
Appropriate power supply voltage is not
applied.
(Operation panel display is not provided.)
Power ON a moulded case circuit breaker
(MCCB), an earth leakage circuit breaker
(ELB), or a magnetic contactor (MC).
—
Check for the decreased input voltage, input
phase loss, and wiring.
Motor is not connected properly.
Check the wiring between the inverter and
the motor.
The jumper across P/+ and P1 is
disconnected.
Securely fit a jumper across P/+ and P1.
When using a DC reactor (FFR-HEL-(H)-E),
remove the jumper across P/+ and P1, and
then connect the DC reactor.
Input signal
Start signal is not input.
Check the start command source, and input a
start signal.
PU operation mode: RUN key
External operation mode: STF/STR signal
Both the forward and reverse rotation start
signals (STF, STR) are input simultaneously.
Turn ON only one of the forward and reverse
rotation start signals (STF or STR).
When the STF and STR signals are turned ON
simultaneously, a stop command is given.
Frequency command is zero.
(RUN LED of the operation panel flickers.)
Check the frequency command source and
enter a frequency command.
AU signal is not ON when terminal 4 is used
for frequency setting.
(RUN LED of the operation panel flickers.)
Turn ON the AU signal.
Turning ON the AU signal activates terminal 4
input.
Output stop signal (MRS) or reset signal (RES)
is ON.
(RUN LED on the operation panel flickers
while MRS signal is ON.)
Turn MRS or RES signal OFF.
Inverter starts the operation with a given
start command and a frequency command
after turning OFF MRS or RES signal. Before
turning OFF, ensure the safety.
Jumper connector of sink - source is wrongly
selected.
(RUN LED of the operation panel flickers.)
Check that the control logic switchover
jumper connector is correctly installed.
If it is not installed correctly, input signal is
not recognized.
Shorting wires between S1 and PC, S2 and PC
are disconnected.
Short between S1 and PC, S2 and PC with
shorting wires.
Voltage/current input switch is not correctly
set for analog input signal (0 to 5 V/0 to 10 V,
4 to 20 mA).
(RUN LED of the operation panel flickers.)
Set Pr. 73, Pr. 267, and a voltage/current input
switch correctly, then input an analog signal
in accordance with the setting.
The STOP/RESET key was pressed
(Operation panel indication is "PS".)
During the External operation mode, check
the method of restarting from a STOP/RESET
key input stop from PU.
Two-wire or three-wire type connection is
wrong.
Check the connection.
Connect STOP signal when three-wire type is
used.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......