Wiring
Control circuit specifications
FR-E700 SC EC/ENE
3 - 25
Wiring connection diagram
To prevent restart at fault occurrence, connect terminals RUN (SAFE 2 signal) and SE to terminals XS0
and XS1, which are the feedback input terminals of the safety relay module.
By setting Pr. 190 "RUN terminal function selection" = "81 (SAFE2 signal)", terminal RUN is turned OFF
at fault occurrence.
I002074E
Fig. 3-16:
Connecting the Safety relay module QS90SR2SN-Q of Mitsubishi
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 192 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
+24V
K1
X0
X1
COM0
COM1
24G
XS0
XS1
Z10
Z00
Z20
Z11
Z01
Z21
K2
R S T
U V W
24 V DC
STOP
Internal Safety
Circuit
Emergency stop button
Output shutoff
circuit
I/O control
START/RESET
FU (SAFE)
햲
Monitor
RUN (SAFE2)
햲
SE
STF
햳
STR (STOP)
햳
S1
S2
PC
PC
Inverter
M
3~
햲
Output signals differ by the setting of Pr. 190 and Pr. 191
(Output terminal function selection).
햳
Input signals differ by the setting of Pr. 178 to Pr. 182
(Input terminal function selection).
Safety relay module
QS90SR2SN-Q
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......