Monitor display and monitor output signals
Parameter
6 - 142
햲
Frequency setting to output terminal status on the PU main monitor are selected by "other mon-
itor selection" of the parameter unit (FR-PU04/FR-PU07).
햳
The cumulative energization time and actual operation time are accumulated from 0 to 65535
hours, then cleared, and accumulated again from 0.When the operation panel is used, the time is
displayed up to 65.53 (65530 h) on the assumption that 1 h = 0.001, and thereafter, it is added up
from 0.
햴
Actual operation time is not accumulated when the cumulative operation time is less than 1h until
turning off of the power supply.
햵
When using the parameter unit (FR-PU04/FR-PU07), "kW" is displayed.
햶
Since the panel display of the operation panel is 4 digits in length, the monitor value of more than
"9999" is displayed "----".
햷
Larger thermal value between the motor thermal and transistor thermal is displayed.
A value other than 0% is displayed if the ambient temperature (heatsink temperature) is high even
when the inverter is at a stop.
Types of Monitor
Unit
Pr. 52
Pr. 158 (AM)
Setting
Terminal AM
Full Scale
Value
Description
Opera-
tion
Panel
LED
PU Main
Monitor
Actual operation
time
햳 햴
1 h
23
—
—
Adds up and displays the inverter oper-
ation time.
You can check the numbers of the mon-
itor value exceeded 65535 h with
Pr. 564. Can be cleared by Pr. 171. (Refer
to page 6-146.)
Motor load factor
0.1%
24
24
200%
Displays the output current value on
the assumption that the inverter rated
current value is 100%.
Monitor value = output power monitor
value/rated inverter current 100 [%]
Cumulative power
햶
0.01 kWh
햵
25
—
—
Adds up and displays the power
amount based on the output power
monitor.
Can be cleared by Pr. 170.
(Refer to page 6-146.)
PID set point
0.1%
52
52
100%
Display the set point, measured value
and deviation during PID control.
(Refer to page 6-293 for details.)
PID measured value
0.1%
53
53
100%
PID deviation value
0.1%
54
—
—
Inverter I/O terminal
monitor
—
55
—
—
—
Displays the ON/OFF status of the
inverter input terminal and output ter-
minal on the operation panel
(Refer to page 6-145 for details.)
Option input terminal
status
—
56
—
—
—
Displays the input terminal ON/OFF sta-
tus of the digital input option
(FR-A7AX-Ekit-SC-E) on the operation
panel. (Refer to page 6-145 for details.)
Option output terminal
status
—
57
—
—
—
Displays the output terminal ON/OFF
status of the digital output option
(FR-A7AY-Ekit-SC-E) or relay output
option (FR-A7AR-Ekit-SC-E) on the
operation panel
(Refer to page 6-145 for details.)
Motor thermal load factor
0.1%
61
61
Thermal re-
lay opera-
tion level
(100%)
Motor thermal heat cumulative value is
displayed.
(Motor overload trip (E.THM) at 100%)
Inverter thermal load
factor
0.1%
62
62
Thermal re-
lay opera-
tion level
(100%)
Transistor thermal heat cumulative
value is displayed.
(Inverter overload trip (E.THT) at 100%)
Tab. 6-35:
Monitor description list (2)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......