CC-Link IE Field Network Basic
Parameter
6 - 358
Details of remote register
●
Remote register (master module to inverter)
햲
When Pr. 37 is not equal to "0", this will be machine speed display (1 increments).
햳
When Pr. 541 "Frequency command sign selection (CC-Link)" = "1", the setting value has
or –. When the setting value is negative, the command is inverted from the starting command.
Setting range: –327.68 Hz to 327.67 Hz (–327.68 to 327.67) 0.01 Hz increments.
For details, refer to page 6-350.
햴
Write data is hexadecimal and only lower two digits are valid. (Upper 2 digits are ignored.)
햵
When Pr. 128 = "50, 51, 60, 61", they are valid. If the data outside the range is set, the previous
setting is retained.
For details, refer to page 6-293.
Device No.
Signal
Description
RWw0
Monitor code1/2
Set the monitor code to be monitored. (Refer to page 6-363.)
By setting "1" in RYC after setting, the specified monitored data is stored in RWr0/
RWr1.
RWw1
Set frequency
앫
Specify the set frequency or machine speed. At this time, whether to write to RAM
or E²PROM is decided with the RYD and RYE settings. After setting the set frequency
in this register, set "1" in RYD or RYE to write the frequency. After writing of
frequency is completed, "1" is set in RXD or RXE in response to the input command.
앫
The setting range is 0 to 400.00 Hz (0.01 Hz increments). Write "40000" when
setting 400.00 Hz.
RWw2
Link parameter extended setting/
Instruction code
Set the instruction code for execution of operation mode rewrite, parameter read/
write, error reference, error clear, etc. (Refer to page 6-361.)
Set "1" in RYF to execute the corresponding instruction after completing the register
setting. "1" is set in RXF after completing the execution of the instruction.
When a value other than "0" is set in Pr. 544 "CC-Link extended setting", upper eight
bits are link parameter extended setting.
Example: When reading Pr.160, instruction code is H0200.
RWw3
Write data
Set the data specified by the RWw2 instruction code. (When required)
Set "1" in RYF after setting RWw2 and this register.
Set zero when the write code is not required.
RWw4
Monitor code 3
Set the monitor code to be monitored. By setting "1" in RYC after setting, the specified
monitored data is stored in RWr
쏔
.
(
쏔
indicates a register number. (RWr4 to 7))
Refer to page 6-363 for monitor code details.
RWw5
Monitor code 4
RWw6
Monitor code 5
RWw7
Monitor code 6
RWw8
Faults history No.
Set the individual fault number of the faults history that you want to read. Up to the
8th previous fault can be read.
Upper digits: H00 (the latest fault) to H07 (8th oldest fault) / lower digits: H00
When any of H08 to HFF is set to the upper digits, the fault record becomes an unde-
termined value.
RWw9
PID set point
Set the PID set point
Setting range : "0 to 100.00 %"
앫
Input a value 100 times greater than the
value to be set.
For example, input "10000" when setting
100.00 %.
앫
Refer to page 6-293 for details of PID
control.
RWwA
PID measured value
Set the PID measured value
Setting range : "0 to 100.00 %"
RWwB
PID deviation
Set the PID deviation.
Setting range : "–100.00 % to 100.00 %"
RWw10,
RWw12,
RWw14,
RWw16,
RWw18
Link parameter extended setting/
Instruction code
Set the instruction code (refer to page 6-361) for execution of operation mode rewrite,
parameter read/write, error reference, error clear, etc. The instructions are executed in
the following order by setting "1" in RYF after completing the register setting: RWw2,
10, 12, 14, 16, then 18. After completing the execution up to RWw18, "1" is set in RXF.
Set HFFFF to disable an instruction by RWw10 to 18. (RWw2 is always executed.)
The first 8 bits are link parameter extended setting.
Example: When reading Pr. 160, instruction code is H0200.
RWw11,
RWw13,
RWw15,
RWw17,
RWw19
Write data
Set the data specified by the instruction code of RWw10, 12, 14, 16, and 18. (when
required)
RWw10 and 11, 12 and 13, 14 and 15, 16 and 17, and 18 and 19 correspond each
other.
Set "1" in RYF after setting the instruction codes (RWw10, 12, 14, 16, and 18) and the
corresponding register.
Set "0" when the write code is not required.
Tab. 6-158:
Remote register definition (master module
씮
inverter)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......