Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 283
6.19.6
Initial settings and specifications of Ethernet communication (FR-E700 SC ENE)
Use the following parameters to perform required settings for Ethernet communication between the
inverter and other devices.
To make communication between other devices and the inverter, perform the initial settings of the in-
verter parameters to match the communication specifications of the devices. Data communication
cannot be made if the initial settings are not made or if there is any setting error.
Pr. No.
Name
Initial Value
Setting Range Description
Parameters referred to
Refer to
Section
442
Default gateway address 1
햲
0
0–255
Enter the IP address of the default gateway, which
is a device connecting the different networks, to
establish a communication between the inverter
and the devices outside the inverter network.
—
443
Default gateway address 2
햲
0
0–255
444
Default gateway address 3
햲
0
0–255
445
Default gateway address 4
햲
0
0–255
805
Ethernet IP address 1
햲
192
0–255
Enter the IP address of the inverter to be connected
to Ethernet.
806
Ethernet IP address 2
햲
168
0–255
807
Ethernet IP address 3
햲
50
0–255
808
Ethernet IP address 4
햲
1
0–255
809
Subnet mask 1
햲
255
0–255
Enter the subnet mask of the network to which the
inverter belongs.
810
Subnet mask 2
햲
255
0–255
811
Subnet mask 3
햲
255
0–255
812
Subnet mask 4
햲
0
0–255
830
Ethernet communication
network number
햲
1
1–239
Enter the network number.
831
Ethernet communication
station number
햲
1
1–120
Enter the station number.
832
Link speed and duplex mode
selection
햲
0
0–4
Set the communication speed and the
communication mode (full-duplex/half-duplex).
833
Ethernet function selection 1
햲
31
0, 10, 20, 30, 31,
36, 38, 9999
Set the application, protocol, etc.
834
Ethernet function selection 2
햲
20
835
Ethernet function selection 3
햲
9999
837
Ethernet IP filter address 1
햲
0
0–255
Set the range of connectable IP addresses for the
network devices.
(When Pr. 837 to Pr. 840 = "0 (initial value)", the
function is invalid.)
838
Ethernet IP filter address 2
햲
0
0–255
839
Ethernet IP filter address 3
햲
0
0–255
840
Ethernet IP filter address 4
햲
0
0–255
841
Ethernet IP filter address 2
range specification
햲
9999
0–255, 9999
842
Ethernet IP filter address 3
range specification
햲
9999
0–255, 9999
843
Ethernet IP filter address 4
range specification
햲
9999
0–255, 9999
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......