Troubleshooting
Causes and corrective actions
FR-E700 SC EC/ENE
7 - 7
Operation panel
indication
PS
FR-PU04
FR-PU07
PS
Name
PU Stop
Description
Stop with the STOP/RESET key of the PU is set in Pr. 75 "Reset selection/disconnected PU detec-
tion/PU stop selection". (For Pr. 75, refer to section 6.17.1.)
Check point
Check for a stop made by pressing the STOP/RESET key of the operation panel.
Corrective action
Turn the start signal off and release with PU/EXT key.
Operation panel
indication
RB
FR-PU04
FR-PU07
RB
Name
Regenerative brake prealarm
Description
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "Special regenerative
brake duty" value. When the setting of Pr. 70 "Special regenerative brake duty" is the initial value
(Pr. 70 = 0), this warning does not occur.
If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV
첸
) occurs.
The RBP signal can be simultaneously output with the [RB] display. For the terminal used for the
RBP signal output, assign the function by setting "7 (positive logic) or 107 (negative logic)" in any
of Pr. 190 to Pr. 192 "Output terminal function selection". (Refer to section 6.10.5.)
Check point
앫
Check that the brake resistor duty is not high.
앫
Check that the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative brake
duty" values are correct.
Corrective action
앫
Increase the deceleration time (Pr. 8).
앫
Check the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative brake
duty" values.
Operation panel
indication
TH
FR-PU04
FR-PU07
TH
Name
Electronic thermal relay function prealarm
Description
Appears if the cumulative value of the Pr. 9 "Electronic thermal O/L relay" reaches or exceeds 85%
of the preset level. If it reaches 100% of the Pr. 9 "Electronic thermal O/L relay" setting, a motor
overload trip (E. THM) occurs. The THP signal can be simultaneously output with the [TH] display.
For the terminal used for THP signal output, assign the function by setting "8 (positive logic) or
108 (negative logic)" in any of Pr. 190 to Pr. 192 "Output terminal function selection"). (Refer to
section 6.10.5.)
Check point
1)Check for large load or sudden acceleration.
2) Is the Pr. 9 "Electronic thermal O/L relay" setting is appropriate? (Refer to section 6.8.1.)
Corrective action
1) Reduce the load weight or the number of operation times.
2) Set an appropriate value in Pr. 9 "Electronic thermal O/L relay". (Refer to section 6.8.1.)
Operation panel
indication
MT
FR-PU04
FR-PU07
—
Name
Maintenance signal output
Description
Indicates that the cumulative energization time of the inverter has reached a given time.
When the setting of Pr. 504 "Maintenance timer alarm output" set time is the initial value (Pr. 504
= 9999), this warning does not occur.
Check point
The Pr. 503 "Maintenance timer" setting is larger than the Pr. 504 "Maintenance timer alarm out-
put set time" setting. (Refer to section 6.21.3.)
Corrective action
Setting "0" in Pr. 503 "Maintenance timer" erases the signal.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......