Misoperation prevention and parameter setting restriction
Parameter
6 - 190
6.17
Misoperation prevention and parameter setting restriction
6.17.1
Reset selection/disconnected PU detection/PU stop selection (Pr. 75)
You can select the reset input acceptance, disconnected PU (FR-PU04/FR-PU07) connector detection
function and PU stop function.
The above parameter can be set when Pr. 160 "User group read selection" = 0.
This parameter allows its setting to be changed during operation in any operation mode even if "0"
(initial value) is set in Pr. 77 "Parameter write selection". Also, if parameter (all) clear is executed, this
setting will not return to the initial value.
Purpose
Parameters that must be set
Refer to
Section
Limit reset function
Make alarm stop when PU is discon-
nected
Stop from PU
Reset selection/
disconnected PU detection/
PU stop selection
Pr. 75
Prevention of parameter rewrite
Parameter write selection
Pr. 77
Prevention of reverse rotation of the
motor
Reverse rotation prevention selection
Pr. 78
Displays necessary parameters
Display of applied parameters and user
group function
Pr. 160,
Pr. 172–Pr. 174
Parameter restriction using password
Password function
Pr. 296
Pr. 297
Control of parameter write by
communication
E²PROM write selection
Pr. 342
Pr. No. Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
75
Reset selection/
disconnected PU detection/
PU stop selection
14
0–3/14–17
For the initial value, reset always enabled,
without disconnected PU detection, and with
PU stop function are set.
250
551
Stop selection
PU mode operation
command source
selection
Pr. 75
Reset Selection
Disconnected PU Detection
PU Stop Selection
0
Reset input always enabled.
If the PU is disconnected, oper-
ation will be continued.
Pressing the STOP key
decelerates the motor to
a stop only in the PU
operation mode.
1
Enabled only when the protective function
is activated
2
Reset input always enabled.
When the PU is disconnected,
the inverter output is shut off.
3
Enabled only when the protective function
is activated
14
(initial value)
Reset input always enabled.
If the PU is disconnected, oper-
ation will be continued.
Pressing the STOP key
decelerates the motor to
a stop in any of the PU,
external and communi-
cation operation modes.
15
Enabled only when the protective function
is activated
16
Reset input always enabled.
When the PU is disconnected,
the inverter output is shut off.
17
Enabled only when the protective function
is activated
Tab. 6-49:
Setting of parameter 75
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......