Selection of operation mode and operation location
Parameter
6 - 220
6.18.3
Start command source and frequency command source during communication
operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551)
When the RS-485 communication with the PU connector or communication option is used, the ex-
ternal start command and frequency command can be made valid. Command source in the PU op-
eration mode can be selected.
From the communication device, parameter unit, etc. which have command source, parameter write
or start command can be executed. Parameter read or monitoring can be executed in any operation
mode.
For FR-A800-E: When the Ethernet connector is used, the command source in the network (NET) / PU
operation mode can be selected.
For the FR-E-700 SC EC the above parameters can be set when Pr. 160 "User group read selection" =
0. However, the parameters can be set whenever the communication option is connected. (Refer to
section 6.17.4.)
햲
This parameter can be changed for the FR-E700 SC EC during a stop in any operation mode.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
338
Communication operation
command source
0
0
Start command source communication
59
79
270
Remote function
selection
Operation mode selection
Stop-on contact control
selection
1
Start command source external
339
Communication speed
command source
0
0
Frequency command source communication
1
Frequency command source external (Frequency
command from communication is invalid, frequency
command from terminal 2 is valid)
2
Frequency command source external (Frequency
command from communication is valid, frequency
command from terminal 2 is invalid)
550
NET mode operation command
source selection
햲
FR-E700 SC EC:
9999
FR-E700 SC ENE:
0
0
The communication option is the command source
when in the NET operation mode.
FR-E700 SC ENE: The Ethernet connector is the
command source when in the NET operation mode.
2
PU connector is the command source when NET
operation mode.
9999
FR-E700 SC EC: Automatic communication option
recognition
Normally, PU connector is the command source.
When a communication option is mounted, the
communication option is the command source.
551
PU mode operation command
source selection
햲
9999
2
PU connector is the command source when PU
operation mode.
3
USB connector is the command source when PU
operation mode.
4
Operation panel is the command source when PU
operation mode.
9999
USB automatic recognition
Normally, operation panel is the command source.
When the parameter unit is connected to the PU
connector, PU is the command source. When USB is
connected, USB connector is the command source.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......