Parameter
Motor brake and stop operation
FR-E700 SC EC/ENE
6 - 107
6.9.4
Stop-on contact control function
(Pr. 6, Pr. 48, Pr. 270, Pr. 275, Pr. 276)
To ensure accurate positioning at the upper limit etc. of a lift, stop-on-contact control causes a me-
chanical brake to be closed while the motor is developing a holding torque to keep the load in contact
with a mechanical stopper etc. This function suppresses vibration which is liable to occur when the
load is stopped upon contact in vertical motion applications, ensuring steady precise positioning.
햲
The parameter can be set when Pr. 160 "User group read selection" = 0.
햳
This parameter allows its setting to be changed during operation even if "0" (initial value) is set in
Pr. 77 "Parameter write selection".
I001567E
Fig. 6-45:
Suppressing vibration in vertical motion applications
Pr. No.
Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
6
Multi-speed setting
(low speed)
10 Hz
0–400 Hz
Sets the output frequency for stop-on-
contact control.
4–6
24–27
15
48
59
72
79
128
178–184
292
Multi-speed setting
Jog frequency
Second stall prevention
operation current
Remote function selection
PWM frequency selection
Operation mode selection
PID action selection
Input terminal
function selection
Automatic acceleration/
deceleration
48
Second stall prevention
operation current
햲
9999
0–200%
Sets the stall prevention operation level
for stall prevention operation level.
9999
Pr. 22 setting
270
Stop-on contact control
selection
햲
0
0
Normal operation
1
Stop-on-contact control
275
Stop-on contact excitation
current low-speed multiplying
factor
햲 햳
9999
0–300%
Set the force (holding torque) for stop-
on-contact control.
Normally set 130% to 180%.
9999
Without compensation
276
PWM carrier frequency at stop-
on contact
햲
9999
0–9
Sets a PWM carrier frequency for stop-
on-contact control.
9999
As set in Pr. 72 "PWM frequency
selection".
AD MFVC
AD MFVC
AD MFVC
GP MFVC
GP MFVC
GP MFVC
Without stop-on-contact control
With stop-on-contact control
Vibration
Complete stop
Lift
Lift
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......