Frequency setting by external terminals
Parameter
6 - 60
6.6
Frequency setting by external terminals
6.6.1
Multi-speed setting operation
(Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
The frequency inverters have 15 fixed setting frequencies (speeds) which can be preset by the user as
required via parameters 4, 5, 6, 24 to 27 as well as via parameters 232 to 239.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX signals).
The above parameters allow its setting to be changed during operation in any operation mode even
if "0" (initial value) is set in Pr. 77 "Parameter write selection".
햲
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Purpose
Parameters that must be set
Refer to
Section
Make frequency setting by combina-
tion of terminals
Multi-speed operation
Pr. 4–Pr. 6,
Pr. 24–Pr. 27
Pr. 232–Pr. 239
Perform jog operation
Jog operatio
Pr. 15, Pr. 16
Infinitely variable speed setting by ter-
minals
Remote setting function
Pr. 59
Pr.
No.
Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
4
Multi-speed setting
(high speed)
50 Hz
0–400 Hz
Set the frequency when RH turns on.
15
59
79
178–184
JOG frequency
Remote function
selection
Operation mode
selection
Input terminal function
selection
5
Multi-speed setting
(middle speed)
30 Hz
0–400 Hz
Set the frequency when RM turns on.
6
Multi-speed setting
(low speed)
10 Hz
0–400 Hz
Set the frequency when RL turns on.
24
Multi-speed setting
(speed 4)
햲
9999
0–400 Hz/9999
Frequency from speed 4 to speed 15 can
be set according to the combination of the
RH, RM, RL and REX signals.
9999: not selected
25
Multi-speed setting
(speed 5)
햲
9999
0–400 Hz/9999
26
Multi-speed setting
(speed 6)
햲
9999
0–400 Hz/9999
27
Multi-speed setting
(speed 7)
햲
9999
0–400 Hz/9999
232
Multi-speed setting
(speed 8)
햲
9999
0–400 Hz/9999
233
Multi-speed setting
(speed 9)
햲
9999
0–400 Hz/9999
234
Multi-speed setting
(speed 10)
햲
9999
0–400 Hz/9999
235
Multi-speed setting
(speed 11)
햲
9999
0–400 Hz/9999
236
Multi-speed setting
(speed 12)
햲
9999
0–400 Hz/9999
237
Multi-speed setting
(speed 13)
햲
9999
0–400 Hz/9999
238
Multi-speed setting
(speed 14)
햲
9999
0–400 Hz/9999
239
Multi-speed setting
(speed 15)
햲
9999
0–400 Hz/9999
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......