Parameter
Motor brake and stop operation
FR-E700 SC EC/ENE
6 - 105
6.9.3
Stop selection (Pr. 250)
Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns off.
Used to stop the motor with a mechanical brake, etc. together with switching off of the start signal.
You can also select the operations of the start signals (STF/STR). (Refer to section 6.10.4 for start signal
selection.)
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Set Pr. 250 to "9999" (initial value) or "8888". The motor decelerates to a stop when the start signal
(STF/STR) turns off.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
Start Signal
(STF/STR)
Stop Operation
250
Stop selection
9999
0–100 s
STF: Forward
rotation start
STR: Reverse rotation
start
The motor is coasted to a stop
when the preset time elapses
after the start signal is turned
off.
7
8
13
Acceleration time
Deceleration time
Starting frequency
1000 s
–
1100 s
STF: Start signal
STR: Forward/reverse
signal
The motor is coasted to a stop
(Pr. 250 1000) s after the
start signal is turned off.
9999
STF: Forward
rotation start
STR: Reverse
rotation start
When the start signal is turned
off, the motor decelerates to
stop.
8888
STF: Start signal
STR: Forward/reverse
signal
I001143E
Fig. 6-43:
Stop operation when parameter 250 = 9999
Output
frequency [Hz]
Start signal
RUN signal
DC brake
Deceleration starts when start signal turns off
Deceleration time (Time set to Pr. 8, etc.)
Time
ON
ON
OFF
OFF
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......