Parameter
Frequency setting by analog input (terminal 2, 4)
FR-E700 SC EC/ENE
6 - 181
Perform operation by analog input current
When the pressure or temperature is controlled constant by a fan, pump, etc., automatic operation can
be performed by inputting the output signal 0/4 to 20 mA of the adjuster to across the terminals 4-5.
Perform forward/reverse rotation by analog input (polarity reversible operation)
Setting "10" or "11" in Pr. 73 and adjusting Pr. 125 (Pr. 126) "Terminal 2 frequency setting gain fre-
quency" (Terminal 4 frequency setting gain frequency) and C2 (Pr. 902) "Terminal 2 frequency setting
bias frequency" to C7 (Pr. 905) "Terminal 4 frequency setting gain" makes reverse operation by ter-
minal 2 (terminal 4) valid.
NOTE
The AU signal must be turned on to use the terminal 4. For the terminal used for AU signal input,
set "4" in any of Pr. 178 to Pr. 184 "Input terminal function selection" to assign the function.
Fig. 6-93:
Frequency setting by the function "Current input
0/4–20 mA" assigned to terminal 4
I001184E
Example
쑴
When performing reversible operation by terminal 2 (0 to 5 V) input.
햲
Set "11" in Pr. 73 to make reversible operation valid.
Set frequency at maximum analog input in Pr. 125 (Pr. 903).
햳
Set 1/2 of the value set in C4 (Pr. 903) in C3 (Pr. 902).
햴
Reversible operation is performed when 0 to 2.5 V DC is input and forward rotation when 2.5 to
5 V DC.
m
P
CAUTION:
When reversible operation is set, be aware of reverse rotation operation when analog input
stops (only the start signal is input).
NOTE
When reversible operation is valid, reversible operation (0 to 4 mA: reverse operation, 4 mA to
20 mA: forward operation) is performed by terminal 4 in the initial setting.
Forward rotation
Frequency
setting
0/4–20 mA DC
Connection diagram
using terminal 4 (0/4–20 mA DC)
Current
input
equipment
Forward
rotation
Not reversible
Reverse
rotation
Reversible
Terminal 2 input [V]
Set frequency [Hz]
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......