Parameter
Selection and protection of a motor
FR-E700 SC EC/ENE
6 - 99
햴
Refer to the following table and set Pr. 83 and Pr. 84.
Pr.
Name
Setting Range
Setting Increments
Initial Value
82
Motor excitation current
(no load current)
0–500 A, 9999
0.01 A
9999
90
Motor constant R1
0–50 , 9999
0.001
9999
91
Motor constant R2
0–50 , 9999
0.001
9999
92
Motor constant L1
0–1000 mH, 9999
0.1 mH
9999
93
Motor constant L2
0–1000 mH, 9999
0.1 mH
9999
94
Motor constant X
0–100%, 9999
0.1%
9999
859
Torque current
0–500 A, 9999
0.01 A
9999
Tab. 6-22:
Setting of parameter 82, 90 to 94 and 859
Pr.
Name
Setting Range
Setting Increments
Initial Value
83
Rated motor voltage
0–1000 V
0.1 V
400 V
84
Rated motor frequency
10–120 Hz
0.01 Hz
50 Hz
Tab. 6-23:
Setting of parameter 83 and 84
NOTE
When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants are used.