Parameter
Function assignment of external terminals
FR-E700 SC EC/ENE
6 - 135
6.10.8
Remote output function (REM, Pr. 495 to Pr. 497)
You can utilize the on/off of the inverter’s output signals instead of the remote output terminal of the
programmable logic controller.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
햲
The above parameters allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending on the Pr. 496 or Pr. 497 setting. The remote out-
put selection can be controlled on/off by computer link communication from the PU connector or by
communication from the communication option.
Set "96" (positive logic) or "196" (negative logic) to any of Pr. 190 to Pr. 192 "Output terminal function
selection", and assign the remote output (REM) signal to the terminal used for remote output.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
495
Remote output selection
0
0
Remote output data clear at
powering off
Remote output data clear
at inverter reset
190–192 Output terminal
function selection
1
Remote output data retention
at powering off
10
Remote output data clear at
powering off
Remote output data
retention at inverter reset
11
Remote output data retention
at powering off
496
Remote output data 1
햲
0
0–4095
Refer to 6-65
497
Remote output data 2
햲
0
0–4095
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......