Causes and corrective actions
Troubleshooting
7 - 12
햲
Available only for three-phase power input specification model.
Operation panel
indication
E.FIN
FR-PU04
FR-PU07
H/Sink O/Temp
Name
Fin overheat
Description
If the heatsink overheats, the temperature sensor is actuated to stop the inverter output.
The FIN signal can be output when the temperature becomes approximately 85% of the heatsink
overheat protection operation temperature. For the terminal used for the FIN signal output,
assign the function by setting "26" (source logic) or "126" (sink logic) in any of Pr. 190 to Pr. 192
"Output terminal function selection". (Refer to section 6.10.5).
Check point
1) Check for too high ambient temperature.
2) Check for heatsink clogging.
3) Check that the cooling fan is stopped. (Check that "FN" is not displayed on the operation
panel.)
Corrective action
1) Set the ambient temperature to within the specifications.
2) Clean the heatsink.
3) Replace the cooling fan.
Operation panel
indication
E.ILF
FR-PU04
Fault 14
FR-PU07
Input phase loss
Name
Input phase failure
햲
Description
Inverter trips when function valid setting (=1) is selected in Pr. 872 Input phase loss protection
selection and one phase of the three phase power input is lost. (Refer to section 6.13.2).
It may function if phase-to-phase voltage of the three-phase power input becomes largely
unbalanced.
Check point
앫
Check for a break in the cable for the three-phase power supply input.
앫
Check that phase-to-phase voltage of the three-phase power input is not largely
unbalanced.
Corrective action
앫
Wire the cables properly.
앫
Repair a break portion in the cable.
앫
Check the Pr. 872 "Input phase failure protection selection" setting.
앫
Set Pr. 872 = "0" (without input phase loss protection) when three-phase input voltage is
largely unbalanced.
Operation panel
indication
E.OLT
FR-PU04
FR-PU07
Stall Prev STP ( OL shown during
stall prevention operation)
Name
Stall prevention
Description
If the output frequency has fallen to 1 Hz by stall prevention operation and remains for 3 s, a fault
(E.OLT) appears and trips the inverter. "OL" appears while stall prevention is being activated.
E.OLT may not occur if stall prevention (OL) is activated during output phase loss.
Check point
Check the motor for use under overload. (Refer to section 6.3.5).
Corrective action
앫
Reduce the load weight.
앫
Check the Pr. 22 "Stall prevention operation level" setting.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......