MODBUS®/TCP (FR-E700 SC ENE)
Parameter
6 - 338
Preset single register (writing data to holding registers) (H06 or 06)
●
The content of the system environmental variables and inverter parameters (refer to MODBUS®
register on page 6-345) assigned to the holding register area can be written.
●
Query message
●
Normal response (Response message)
●
Query message setting
●
Content of normal response
With a normal response, the contents in the response are the same as those in
쐃
to
쐆
of the
query message.
쐃
Transaction
identifier
쐇
Protocol
identifier
쐋
Length field
쐏
Unit
identifier
쐄
Function
쐂
Register
address
쐆
Preset data
H
(8 Bits)
L
(8 Bits)
H
(8 Bits)
L
(8 Bits)
H
(8 Bits)
L
(8 Bits)
(8 Bits)
H06
(8 Bits)
H
(8 Bits)
L
(8 Bits)
H
(8 Bits)
L
(8 Bits)
쐃
Transaction
identifier
쐇
Protocol
identifier
쐋
Length field
쐏
Unit
identifier
쐄
Function
쐂
Register
address
쐆
Preset data
H
(8 Bits)
L
(8 Bits)
H
(8 Bits)
L
(8 Bits)
H
(8 Bits)
L
(8 Bits)
(8 Bits)
H06
(8 Bits)
H
(8 Bits)
L
(8 Bits)
H
(8 Bits)
L
(8 Bits)
Message
Description
쐃
Transaction identifier
The master adds the data for the purpose of transaction control.
The same data is returned in the response from the slave.
쐇
Protocol Identifier
Fixed to 0. (When the slave receives data other than 0, it does not send the response
message.)
0 is returned in the response from the slave.
쐋
Length field
The data length from the unit identifier to the data is stored in byte.
쐏
Unit identifier
Fixed to 255
쐄
Function
Set H06.
쐂
Register address
Set the holding register address to write data to.
Register address = holding register address (decimal) - 40001
For example, when register address 0001 is set, data is written to holding register address
40002.
쐆
Preset data
Set the data to write to the holding register. Write data is fixed at 2 bytes.
Tab. 6-126:
Explanation of the query message
Example
쑴
Write 60 Hz (H1770) to register 40014 (running frequency RAM) in the inverter.
Query message
Normal response (Response message)
The same data as those in the query message
쑶
Transaction
identifier
Protocol
identifier
Length field
Unit identifier
Func-
tion
Register address
Preset data
햲
햲
H00
(8 Bits)
H00
(8 Bits)
H00
(8 Bits)
H06
(8 Bits)
HEF
(8 Bits)
H06
(8 Bits)
H00
(8 Bits)
H0D
(8 Bits)
H17
(8 Bits)
H70
(8 Bits)
햲
A given value is set.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......