Limit the output frequency
Parameter
6 - 54
6.4.2
Avoid mechanical resonance points (frequency jumps) (Pr. 31 to Pr. 36)
When it is desired to avoid resonance attributable to the natural frequency of a mechanical system,
these parameters allow resonant frequencies to be jumped.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Up to three areas may be set, with the jump frequencies set to either the top or bottom point of each
area.
The settings of frequency jumps 1A, 2A, 3A are jump points, and operation is performed at these fre-
quencies in the jump areas.
Pr. No. Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
31
Frequency jump 1A
9999
0–400 Hz/9999
1A to 1B, 2A to 2B, 3A to 3B is
frequency jumps
9999: Function invalid
—
32
Frequency jump 1B
9999
0–400 Hz/9999
33
Frequency jump 2A
9999
0–400 Hz/9999
34
Frequency jump 2B
9999
0–400 Hz/9999
35
Frequency jump 3A
9999
0–400 Hz/9999
36
Frequency jump 3B
9999
0–400 Hz/9999
Fig. 6-11:
Definition of the jump areas
I000019C
Set frequency
Output fr
equenc
y