8 Parameterization
122
Italics = Parameter can only be viewed in the "Advanced" password level
Italics = Parameter can only be viewed in the "Advanced" password level
Italics = Parameter can only be viewed in the "Advanced" password level
Auto Adjust
Prior to starting the zero point adjustment, make sure that:
•
There must be no flow through the sensor (close all valves, shut-off devices, etc.).
•
The sensor must be completely filled with the medium to be measured.
Menu/parameter
Value range
Description
Device Setup/... Transmitter/
... Low Flow Cut Off
Threshold
0 to 10 %
Select the switching threshold for monitoring the low
flow
If the value falls below the set switching threshold, no
flow is measured. The current output is set to zero.
The switching threshold of the low flow monitoring re-
fers to the measuring range currently set.
Default setting: 1 %
Hysteresis
0 to 50 %
Hysteresis setting of the low flow
Menu/parameter
Value range
Description
Device Setup/... Transmitter/
... Operating Mode
Meter Mode
Forward only, Forward and
Reverse
Measuring direction setting for the sensor
•
"Forward only": the device only measures and
counts in the supply direction
•
"Forward an Reverse": the device measures and
counts in both directions
Default setting: Forward an Reverse
Flow Indication
Normal, Reverse
Inverts the indicated flow direction
Default setting: Normal
Menu/parameter
Value range
Description
Device Setup/... Transmitter/
... System Zero
Manual Adjust
-50 to +50 mm/s
Entry of the flow velocity for the system zero
Auto Adjust
Start the automatic zero point adjustment
?
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......