8 Parameterization
138
Italics = Parameter can only be viewed in the "Advanced" password level
Menu/parameter
Value range
Description
Diagnostics/Diagnostics Control/
Sensor Measurements
One Shot Sensor Mea
Start of measurement
The measured values for the start moment are re-
corded
Coil Current
Display only
Display of the coil current
Coil Resistor
Display only
Display of the coil resistor
Coil Voltage
Display only
Display of the coil voltage
Coil R. Max Alarm
0 to 1000 Ω
Setting of the maximum limit value for the coil resistor
When this value is exceeded, an alarm is triggered.
Default setting: 1000 Ω
Coil R. Min Alarm
0 to 1000 Ω
Setting of the minimum limit value for the coil resistor
When this value is not reached, an alarm is triggered.
Default setting: 0 Ω
Signal-Cable length
0.01 to 200 m
Entry of the Signal-Cable length between the trans-
mitter and the sensor
For compact devices, 0.01 m must be entered.
Default setting: 0 m
Sensor Temp Value
a
Display only
Display of sensor temperature.
Adj. Sensor Temp Value
a
-50 to +200°C
The sensor temperature must be calibrated to the lo-
cal conditions. The temperature measured using a
separate measuring device can be entered here.
Sensor T. Max. Alarm
a
-50 to +200 C°
Setting of the maximum limit value for the sensor
temperature. When this value is exceeded, an alarm
is triggered.
Default setting: +200 C°
Sensor T. Min. Alarm
a
-50 to +200 C°
Setting of the minimum limit value for the sensor tem-
perature. When this value is not reached, an alarm is
triggered.
Default setting: -50 C°
a
Only available for JUMO flowTRANS MAG S02/H02
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......