5 Electrical connection
64
5.7
Electrical data
5.7.1
Current/HART output
Terminal Function
31/32
Current/HART output
- The current output is available in "active" or "passive" mode.
97/98
PROFIBUS-PA (PA+/PA-) or FOUNDATION Fieldbus (FF+/FF-)
- according to IEC 61158-2
51/52
Digital output DO1 active/passive
- Function can be configured using software on-site as "Pulse out-
put" or "Binary output". The default setting is "Pulse output".
81/82
Digital input/contact input
- Function can be configured using software on-site as "External output
switch-off", "External counter reset", "External counter stop", or "Other".
41/42
Digital output DO2 passive
- Function can be configured using software on-site as "Pulse output" or
"Binary output". The default setting is "Binary output", flow direction signaling.
FE
Functional ground
Max. admissible burden (R
B
) de-
pending on the source voltage (V
2
)
The current/HART output is available in "active" or "passive" mode.
A
= "Active" configuration:
4 to 20 mA, HART protocol (standard), load: 250 Ω ≤ R ≤ 650 Ω
B
= "Passive" configuration:
4 to 20 mA, HART protocol (standard), load: 250 Ω ≤ R ≤ 650 Ω
Voltage supply for the current output: minimum 11 V, maximum 30 V
Operation in Ex-zone 1
Maximum burden 300 Ω
I = internal, E = external
G
00
4
7
5
-
01
+
3
1
-
32
I
E
A
R
B
+
3
1
-
32
I
E
V
B
R
B
U
1
U
2
G0059
2
2
00
2
50
300
350
400
450
500
550
600
650
700
17
18
19
20
21
22
23
24
25
26
27
28
29
30
U [V]
2
R
[]
B
Ω
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......