55
5 Electrical connection
5.3
Assembling the signal and magnet coil cable - single-compartment
housing
Assemble the cable end on the transmitter side as displayed in the figure.
IMPORTANT (NOTE)!
Use ferrules.
•
Ferrules 0.75 mm2 (AWG 19), for the shielding (1S, 2S)
•
Ferrules 0.5 mm2 (AWG 20) for all other wires
•
Twist the wire mesh shield of the cable and connect to the grounding terminal.
•
Connect the ground wire of the cable to the SE clamp of the terminal strip.
•
Connect all other wires as displayed in the figure below.
CAUTION – Device damage!
The shields may not touch. Otherwise, a signal short circuit occurs.
Transmitter side
(1)
Ground wire
(2)
Wire mesh shield
(4)
Twisted wire mesh shield
Terminal
Description, wire color
Length in mm (inch)
M1
Magnet coil, brown
70 (2.76)
M2
Magnet coil, red
70 (2.76)
D1
Data line, orange
70 (2.76)
D2
Data line, yellow
70 (2.76)
SE
Shielding
-
3
Measurement potential, green
70 (2.76)
2S
Shield of E2
60 (2.36)
E2
Signal line, blue
60 (2.36)
E1
Signal line, violet
60 (2.36)
1S
Shield of E1
60 (2.36)
G01323
M1 M2 D1 D2
SE
3 2S E2 E1 1S
(1)
(2)
(4)
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......