6 Digital communication
6.3
FOUNDATION Fieldbus (FF)
For further information
see the separate interface description.
6.3.1
System integration
The following are required:
•
DD (device description) file, containing the device description.
•
CFF (Common File Format) file; this is required for engineering the segment. Engineering can occur
online or offline
B
= Linking Device (incl. bus voltage supply and terminator)
Interoperability test campaign no.
ITK 5.20
Manufacturer ID
0x000320
Device ID
0x0124
Configuration
Directly on device
Via services integrated in the system
National configurator
Transmission signal
According to IEC 61158-2
Bus topology
•
Tree and/or line structure
•
Bus termination: passive on both ends of the main bus line (RC element
R = 100 Ω, C = 1 µF)
Voltage and current consumption
•
Mean current consumption: 10 mA
•
In case of a fault, the FDE (fault disconnection electronic) function built
into the device ensures that the current consumption can rise to a maxi-
mum of 13 mA.
•
The upper current limit is electronically limited.
•
The voltage on the bus line must be in the range between DC 9 and 32 V.
Bus address
The bus address is assigned automatically, or can be set manually on the
system.
The identifier (ID) is formed as a unique combination of the instrument ID, de-
vice ID and device serial no.
IMPORTANT (NOTE)!
The files required for operation are included on the CD, or can be downloaded from www.jumo.de.
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......