8 Parameterization
128
Italics = Parameter can only be viewed in the "Advanced" password level
Italics = Parameter can only be viewed in the "Advanced" password level
Menu/parameter
Value range
Description
Input/Output/... Logic Setup/
... DO1 Alarm Config
General Alarm
ON/OFF
Each alarm can be enabled separately. This allows
you to individually configure when the digital output
DO1 signals an alarm.
Min. Flowrate Alarm
ON/OFF
Max. Flowrate Alarm
ON/OFF
Empty Pipe
ON/OFF
TFE Alarm
ON/OFF
Gas Bubble
a
ON/OFF
Conductivity
a
ON/OFF
Coating
a
ON/OFF
Sensor Temp
a
ON/OFF
a
Only available for JUMO flowTRANS MAG S02/H02
Menu/parameter
Value range
Description
Input/Output/... Logic Setup/
... DO2 Alarm Config
-
-
See description "....DO1 Alarm Config"
Menu/parameter
Value range
Description
Input/Output/
... Pulse Setup
Operating Mode
Pulse Mode, Fullscale Fre-
quency
The menu is only displayed after selecting a "Pulse
..." function below "Input/Output/... Setup Digital
outp./Function DO1/DO2".
Operating mode selection for the digital output
You can choose between two operating modes:
•
"Pulse Mode": in pulse mode, pulses per unit are
output (e.g. 1 pulse per m
3
)
•
"Frequency mode": In frequency mode, a fre-
quency proportional to the flow is output; the
maximum frequency can be configured according
to the measuring range end value (maximum
5 kHz).
Default setting: "Pulse Mode"
Pulses per Unit
1 to 5250/s
Pulse setting per unit in the "Pulse Mode" operating
mode
Pulse Width
0.1 to 2000 ms
Pulse Width setting in the "Pulse Mode" operating
mode
The pulse factor and pulse width are interdependent
and are calculated dynamically.
Limit Frequency
Display only
Display of pulse output limit frequency
Fullscale Frequency
0 to 5000 Hz
Frequency setting for the measuring range end value
in "Fullscale Frequency"
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......