5 Electrical connection
56
5.4
Sensor connection
5.4.1
Metal terminal boxes
The connection must only be established when the voltage supply is switched off.
The device must be grounded according to the regulations. The sensor must be connected to the trans-
mitter via the signal cable (part no. 00648906).
IMPORTANT (NOTE)!
Use ferrules.
•
Ferrules 0.75 mm
2
(AWG 19), for the shielding (1S, 2S)
•
Ferrules 0.5 mm
2
(AWG 20) for all other specifications
•
Uncover the wire mesh of the cable and connect to the grounding clamp with the ground wire.
•
Connect all other wires as shown in the following figure.
CAUTION – Property damage!
The shields may not touch. Otherwise, a signal short circuit occurs.
(1)
Ground wire
(2)
Grounding clamp
(4)
Shielding mesh
Terminal
Description, wire color
M1
Magnet coil, brown
M2
Magnet coil, red
D1
Data line, orange
D2
Data line, yellow
PE
Shielding
3
Measurement potential, green
2S
Shield of E2
E2
Signal line, blue
E1
Signal line, violet
1S
Shield of E1
G00
67
1
-
02
1S E1 E2 2S
3 D2 D1 M2 M1
1S E1 E2 2S 3 D2 D1 M2 M1
(1)
(2)
(4)
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......