8 Parameterization
134
Italics = Parameter can only be viewed in the "Advanced" password level
PA Addr (-BUS-)
DIP switch (only for transmitter in a dual-compartment housing):
•
DIP switches 1 to 7 determine the PROFIBUS address
•
DIP switch 8 determines the address mode:
DIP switch 8 = Off = The address is set via the bus or via menus using the device keyboard, then "-
BUS-" appears on the display
DIP switch 8 = On = The address is set via the DIP switches 1 to 7, then "(HW Switch)" appears on
the display.
The address switch setting is adopted when the device is restarted, not during ongoing operation
Default setting for DIP switch 8: off
Menu/parameter
Value range
Description
Communication/
PROFIBUS
The menu is only displayed for devices with PROFI-
BUS-PA.
AO-Density
Display only
Current output value for the density from the trans-
ducer block flow including status
DI-Alarm Info
Display only
Current output value including status
The channel can be selected with the "DI Channel"
parameter
DI-Channel
Maintenance, Out of Spec,
Function Check, Failure
Selection of the "DI Alarm Info" output by the channel
DO-Cyclic Control
Display only
Current function including status
The function can be selected with the "DO Channel"
parameter.
DO-Channel
Off, Totalizer Reset (all),
Flowrate to Zero, System
Zero Adjust, Totalizer Stop
(all), Dual range
a
, Start/Stop
Batching
a
Selection of function "DO Cyclic Control"
a
Only available for JUMO flowTRANS MAG S02/H02
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......