129
8 Parameterization
Italics = Parameter can only be viewed in the "Advanced" password level
Menu/parameter
Value range
Description
Input/Output/
Current Output
lout at Alarm
High Alarm, Low Alarm
Selection of the status for the current output in case
of a fault
The output "low" or "high" current is set in the follow-
ing menu.
Default setting: High
Low Alarm Value
3.5 to 3.6 mA
Selection of the current for Low Alarm
Default setting: 3.5 mA
High Alarm Value
21 to 23 mA
Selection of the current for High Alarm
Default setting: 21.8 mA
lout at EP Alarm
Off, Q = 0 %, High Alarm, Low
Alarm
Selection of the status for the current output in case
of an empty pipe
•
Off: the error is not output via the current output
•
Q = 0 %: the current output assumes the value for
"No flow"
•
High Alarm: the current output assumes the value
for "High Alarm"
•
Low Alarm: the current output assumes the value
for "Low Alarm"
Default setting: off
lout at Flow > 103%
Off, High Alarm, Low Alarm
Selection of the status for the current output if the val-
ue falls below the measuring range end value
•
Off: the error is not output via the current output
•
High Alarm: the current output assumes the value
for "High Alarm"
•
Low Alarm: the current output assumes the value
for "Low Alarm"
Default setting: Off
lout at TFE Alarm
Off, Q = 0 %, high alarm, low
alarm
Selection of the status for the current output in case
of a partial filling alarm
•
Off: the error is not output via the current output
•
Q = 0 %: the current output assumes the value for
"No flow"
•
High Alarm: the current output assumes the value
for "High Alarm"
•
Low Alarm: the current output assumes the value
for "Low Alarm"
Default setting: Off
Iout Mode
4 to 20 mA, 4 to 12 to 20 mA Operating mode selection for the current output
•
4 to 20 mA:
4 mA = No flow
20 mA = Maximum flow
•
4 to 12 to 20 mA:
4 mA = Maximum reverse flow
12 mA = No flow
20 mA = Maximum forward flow
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......