69
6 Digital communication
6
Digital communication
6.1
HART protocol
The transmitter uses HART protocol (HART 5) for digital communication.
For further information
see the separate interface description.
6.1.1
System integration
The communication (configuration, parameterization) can be carried out in conjunction with the DTM
(Device Type Manager) available for the device and the corresponding framework applications accord-
ing to FDT 1.21.
Configuration
Directly on device
Via DTM in connection with the framework application
Transmission
FSK modulation on current output
4 to 20 mA according to Bell 202 standard
Max. signal amplitude
1.2 mA
ss
Burden for current output
min. 250 Ω, max. = 560 Ω
Cable
AWG 24 twisted
Max. cable length
1500 m
Baud rate
1200 baud
View
Log 1: 1200 Hz
Log 0: 2200 Hz
IMPORTANT (NOTE)!
The necessary device DTM is included on the CD and can be downloaded from www.jumo.de.