8 Parameterization
114
Italics = Parameter can only be viewed in the "Advanced" password level
Italics = Parameter can only be viewed in the "Advanced" password level
Cable length
The input is required here for devices of the JUMO flowTRANS MAG S02/H02 design type to be able to
use the diagnostic function.
If the ScanMaster verification software is used, the signal cable length must also be input.
Manual/Automatic
Prior to starting the zero point adjustment, make sure that:
•
There must be no flow through the sensor (close all valves, shut-off devices, etc.).
•
The sensor must be completely filled with the medium to be measured.
Damping
0.02 to 60 s
Damping selection
The value set here refers to 1 t (tau).
The specification refers to the response time for a
sudden change in the flow. It affects the current value
in the LCD display and the current output.
Default setting: 1 second
lout at Alarm
Low, High
Current output status in case of a fault
The value for "low" or "high" is set in the following
menu.
Default setting: High
Low Alarm Value
3.5 to 3.6 mA
Current in case of low alarm
Default setting: 3.5 mA
High Alarm Value
21 to 23 mA
Current in case of high alarm
Default setting: 21.8 mA
System Zero
Selection of the "System Zero" submenu
Cable length
0.01 to 200 m
Entry of the signal cable length between the transmit-
ter and the sensor
For compact devices, JUMO flowTRANS MAG S/H,
0.01 m must be entered.
Menu/parameter
Value range
Description
?
Menu/parameter
Value range
Description
Easy Setup/
System Zero
"System zero point" submenu
Manual
Starts the manual zero point adjustment
Automatic
Start the automatic zero point adjustment
?
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......