7 Startup
90
Entry of the signal cable length between the transmitter and the sensor. For compact devices, 0.01 m
must be entered.
43. Use
to confirm your setting.
44. Use
to switch to the process display
The main menu is displayed again after all parameters are set. The most important parameters are
now set.
The LCD display is provided with capacitive push-buttons. These allow you to operate the device through
the closed lid.
Menu Q
max
(measuring range end value)
Default setting of additional parameters (provided no customer-specific parameterization has
been performed)
Menu
Easy Setup
Exit
Select
IMPORTANT (NOTE)!
For additional information regarding operation of the LCD display, refer to chapter 8.1 "Operation",
page 95.
For a detailed description of all the menus and parameters, see chapter 8.4 "Parameter description",
page 113.
IMPORTANT (NOTE)!
The transmitter automatically calibrates the capacitive push-buttons on a regular basis. If the housing is
opened during operation, the sensitivity of the push-buttons is first increased meaning that operating er-
rors may occur. The sensitivity of the push-buttons returns to normal during the next automatic calibra-
tion.
IMPORTANT (NOTE)!
The device is set to the measuring range end value Q
max
DN at the factory provided there are no other
customer specifications. Measuring range end values that correspond to a flow velocity from 2 to 3 m/s
(0.2 to 0.3 × Q
max
DN) are ideal.
The smallest and largest possible configurable measuring range end values are provided in the table in
chapter 7.6 "Nominal width, measuring range", page 92.
Possible parameterization
Default setting
Q
max
Depending on the nominal width
(
Chapter 7.6)
Q
max
DN
(
Chapter 7.6)
Sensor TAG
Alphanumeric
Max. 20 characters
None
Sensor Location TAG
Alphanumeric
Max. 20 characters
None
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......