83
7 Startup
7.4.3
Setting the bus address
The bus address for the FOUNDATION Fieldbus is assigned automatically by the LAS (Link Active
Scheduler). Address detection relies on a unique number (DEVICE_ID). The number is composed of the
manufacturer ID, device ID and device serial number.
The switch-on behavior is compliant with draft DIN IEC/65C/155/CDV from June 1996.
The device's mean current consumption is 10 mA.
The voltage on the bus line must be in the range between DC 9 and 32 V.
IMPORTANT (NOTE)!
The upper current limit is electronically limited. In case of a fault, the FDE (fault disconnection electronic)
function built into the device ensures that the current consumption can rise to a maximum of 13 mA.