7 Startup
7.5.2
Error message "Incompatible sensor"
If the transmitter is operated with a sensor of another series, the following error message appears on the
transmitter display:
A flow of ZERO is indicated in the process display. No flow measurement is performed.
1. Use
to switch to the information level.
2. Use
or
to select the "Diagnostics" submenu.
3. Use
to confirm your selection.
When trying to start up a mixed installation, the adjacent error message appears. The device cannot per-
form measurements. The display for the current flow is ZERO. The current output assumes its pre-con-
figured state (Iout for alarm).
Make sure that the sensor and the transmitter are of the same device version (e.g., sensor 406012/2-0
JUMO flowTRANS MAG S, transmitter 406018/2-0 JUMO flowTRANS MAG S).
IMPORTANT (NOTE)!
When starting up the device, make sure that the transmitter and the sensor are assigned correctly. A
mixed operation of different sensors and transmitter versions is not possible. (
see
chapter 7.1 "Checks prior to start-up", page 73)
Boiler 9
Q
0.00
l/min
Σ+
1403.09
m3
Σ-
591.74
m3
Sensor
-Operator Menu-
Diagnostics
Operator Page 1
Operator Page
2
Back
Select
Sensor
-- F
2
48.036--
Incompatible sns
Tx+snr are not
the same series
Back
Exit
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......