10 Error messages
168
F244.031
Electronics
Internal supply voltage er-
ror
lout at alarm
General Alarm 0 Hz
0 %
No
Contact service
F236.024
Operation
DC to High
lout at alarm
General Alarm 0 Hz
0 %
No
Lot of NV-Resets
Refer to instr. Manual
F232.022
Electronics
Driver Error Uref = 0
lout at alarm
General Alarm 0 Hz
0 %
No
Check wiring for open cir-
cuit
Check fuse
F228.020
Electronics
Error in coil circuit
lout at alarm
General Alarm 0 Hz
0 %
No
Check wiring
for short-circuit
F226.019
Electronics
ADC saturated
lout at alarm
General Alarm 0 Hz
0 %
No
Empty pipe?
Galvanic voltage?
C190.045
Configuration
An alarm is simulated
Switch off alarm simulation
Current value
No response
Current
value
Current
value
No
C186.009
Configuration
Tx Simulator/Calibrator
mode
Current value
Current value
Current
value
Current
value
Mask group
Switch off Calibrator mode
C185.030
Operation
Hold last good knwon value Current value
No response
Current
value
Current
value
Mask group
Switch off noise reduction
Contact service
C184.010
Configuration
The Flowrate is set to zero 4 mA (0 %
flow)
No response
0 Hz
0 %
Mask group
Check digital in terminals
81, 82
C182.008
Configuration
Flow simulation
Current value
or High Alarm
(flow > 105 %)
No response,
Min/Max or
General Alarm
Current
value
Current
value
Mask group
Switch off Simulation Mode
C178.000
Configuration
Simulated/Fixed Current
Output
Simulated val-
ue
No response
Current
value
Current
value
Mask group
Simulation Mode?
HART address > 0?
C177.015
Configuration
HART Addr. <>0
4 mA
Current value
Current
value
Current
value
Mask group
Multidrop mode
Set HART Addr. = 0
C176.011
Configuration
Totalizer Stop
Current value
No response
0 Hz
Current
value
Mask group
Check digital in terminals
81, 82
C175.013
Configuration
Totalizer Reset
Current value
No response
Current
value
Current
value
Mask group
Check digital in terminals
81, 82
C174.02
Configuration
Pulse Simulation selected
on DO1
Current value
No response
Simulated
value
Current
value
Mask group
Switch off Simulation Mode
Error no./
area
Text in the
LCD display
Current
output
behavior
Digital
output
behavior
Pulse
output
behavior
Display
Error
can be
masked?
Содержание flowTRANS MAG H01
Страница 2: ......
Страница 22: ...1 Safety 22...
Страница 68: ...5 Electrical connection 68...
Страница 72: ...6 Digital communication 72...
Страница 94: ...7 Startup 94...
Страница 108: ...8 Parameterization 108...
Страница 109: ...109 8 Parameterization...
Страница 110: ...8 Parameterization 110...
Страница 111: ...111 8 Parameterization...
Страница 112: ...8 Parameterization 112...
Страница 152: ...8 Parameterization 152...
Страница 160: ...9 Advanced diagnostics functions 160...
Страница 258: ...14 Annex 258...
Страница 259: ......