3500/42 Operation and Maintenance
Configuration Information
61
Integrate
When Integrate is enabled, the Direct Full-scale Range selections change to
the following:
The Direct values (Integrated) are available for all transducer types.
Full-scale Range –
Direct
0-5 mil pp
0-10 mil pp
0-20 mil pp
0-100
µ
m pp
0-200
µ
m pp
0-500
µ
m pp
Custom
Clamp Value
The value that a proportional value goes to when that channel or proportional
value is bypassed or defeated (for example a problem with the monitor). The
selected value can be between the minimum and maximum full-scale range
values. Only the values available from the Recorder Outputs,
Communication Gateway and Display Interface Module are clamped to the
specified value when the proportional value is invalid.
Recorder Output
The proportional value of a channel that is sent to the 4 to 20 mA recorder.
The recorder output is proportional to the measured value over the channel
full-scale range. An increase in the proportional value that would be
indicated as upscale on a bar graph display results in an increase in the
current at the recorder output. If the channel is bypassed, the output will be
clamped to the selected clamp value or to 2 mA (if the 2 mA clamp is
selected).
Corner Frequencies
High-pass Filter
A four-pole filter that must be at least a decade away from the Low-pass
Filter.
HPF = High-pass Filter; LPF = Low-pass Filter
HPF
≤
( LPF / 10 )
Low-pass Filter
A four-pole filter that must be at least a decade away from the High-pass
Filter.
HPF = High-pass Filter; LPF = Low-pass Filter
LPF
≥
( HPF * 10 )