3500/42 Operation and Maintenance
Specifications
213
ALARMS
Alarm Setpoints:
Alert levels can be set for each value
measured by the monitor. In addition,
Danger setpoints can be set for any two of
the values measured by the monitor. All
alarm setpoints are set using software
configuration. Alarms are adjustable and
can normally be set from 0 to 100 % of Full
Scale for each measured value. The
exception is when the Full Scale range
exceeds the range of the transducer. In this
case, the set point will be limited to the
range of the transducer. Accuracy of alarms
are to within 0.13 % of the desired value.
Alarm Time Delays:
Alert:
Danger:
Alarm delays can be programmed using
software, and can be set as follows:
From 1 to 60 seconds in 1 second intervals.
0.1 seconds (typical) or from 1 to 60
seconds in 1 second intervals.