Configuration Information
3500/42 Operation and Maintenance
58
- Monitors must be configured in channel pairs (for example, Channels 1 and 2
may be configured as Velocity and Channels 3 and 4 may be configured as
Thrust Position).
- When integration is selected, the available Direct Full-scale Ranges will change
to reflect this.
- When band-pass filtering is selected, the high-pass and low-pass filters must be
set a minimum of a decade apart.
- The 100ms danger alarm is only available for the Velomitor and High
Temperature Velomitor options.
- When a single or dual channel of velocity is activated, the maximum channel
frequency supported is as shown:
Configuration Settings
Channel
Frequencies
Filtering
RMS
Integration
3 to 5500 Hz
---
No
---
10 to 5500 Hz
---
Yes
---
** dashes represent both yes and no
- The Latching OK Mode and the Timed OK Channel Defeat options are not
compatible.
- If a Non-Standard transducer is selected, the setpoint OK limits are set to ±1
volt from the Upper and Lower OK limits that are selected.
- If the monitor is configured to alarm on high velocity conditions on a
reciprocating machine, it is recommended that you disable the Timed
OK/Channel Defeat option.